Honeywell UMC800 User Manual

Page 43

Advertising
background image

Mounting and Wiring

Signal Wiring

Release F

UMC800 Controller Installation and User Guide

35

4/01

Pulse frequency card outputs

The pulse frequency card outputs are open collector drivers designed to drive a maximum of 100 mA. All
Pulse Frequency card digital outputs are optically isolated from each other. The maximum supply voltage
must not exceed 27 Volts dc.

V Supply (DC) 27 V Max

V Return (DC)

Pulse / Frequency Input Card

DO connections

+

+

I

L

(100mA Max)

Figure 22 Pulse/frequency card digital output connections