Mounting and Wiring
Wiring Communication Links

40

UMC800 Controller Installation and User Guide

Release F

4/01

DISPLAY connector (to operator interface)

The controller is connected to the operator interface through a 15-pin D-Type connector cable. One cable
end is connected to the DISPLAY connector of the controller. The other end connects to a 10-pin in-line
connector at the rear of the operator interface case. This cable end must be made, since some installations
may require the cable to be run through conduit. Table 13 shows the pinouts for the operator interface end
of the cable. Figure 25 shows the connector location at the rear of the operator interface.

Table 13 Operator interface connector pinouts

Operator Interface Connector Wiring

Signal Name

Wire Color

Terminal No.

Receive –
Receive +

Black
White

1
2

Receive Shield
Transmit Shield

Shield
Shield

3

Transmit –
Transmit +

Black
Red

4
5

Signal Ground
Signal Ground

Black
Green

6

Outer Shield
- - - - - - - -

Shield
- - - - -

7
8

+24 Vdc *
+24 Vdc *

Black
Blue

9

10

*

CAUTION: For 24 Vdc, make sure that the wiring is on terminals #9 and
#10.
The CPU board may be damaged if the wiring is accidentally connected
to terminals #1 and #2.