Mounting and Wiring
Wiring Communication Links

42

UMC800 Controller Installation and User Guide

Release F

4/01

COMM A and B connectors (optional)

The CPU module equipped with the optional communication board provides two additional RS 485
communications ports with Modbus RTU protocol support. COMM A port allows the UMC800 controller
to network with up to 31 other slave UMC800 controllers and devices on a Modbus link. COMM B port
allows the UMC800 controller to be a master to up to 16 slave UMC800 controllers and devices on a
Modbus link.

Figure 26 shows the COMM A and B connector wiring when using either a shielded twisted pair or 4-wire
shielded cable.

NOTE: When using the RS 485 communications, it is recommended that an RS 485 to RS 232 converter
(such as Black Box model IC901A) be used to interface with the host PC. Also, be certain that the Half
Duplex Turnaround Delay parameter for the converter set to 1 millisecond or less.

C

O

MM A

Shield

+

_

Transmit

Receive

+

_

2-Wire

Shielded

Shield

+

_

Transmit

Receive

+

_

4-Wire

Shielded

C

O

MM A

C

O

MM B

Shield

+

_

Transmit

Receive

+

_

Shield

+

_

Transmit

Receive

+

_

C

O

MM B

Figure 26 COMM A and B port wiring (2-wire and 4-wire)

ATTENTION

Make sure you connect the correct polarity. If the TX+ and TX– connections are reversed from
the correct connections, an error message will be generated when attempting to do any
communications and the program then self-terminates.