Mounting and Wiring

Remote Access

Release F

UMC800 Controller Installation and User Guide

47

4/01

Step

Action

9

Set the modem switches to the following:

Switch

Setting

Position

Function

1

ON

DOWN

Modem ignores DTR (Override)

2

OFF

UP

Verbal (word) results

3

OFF

UP

Suppresses result codes

4

ON

DOWN

Suppresses echo

5

OFF

UP

Modem answers on first ring

6

ON

DOWN

CD always ON (Override)

7

OFF

UP

Loads Y0-Y4 configuration from user-defined
nonvolatile memory (NVRAM)

8

OFF

UP

Disables command recognition (dumb mode)

10

Connect the modem to the RS232 port of the UMC800 using a DB-25 male to DB-9 male
RS232 cable. Null modem cable may not work.

11

Connect the modem to a telephone jack.

12

Power up the modem and the UMC800.

13

On a remote computer, run Control Builder software.

14

Setup Control Builder to dial the UMC800.

15

Verify that communications is established with the remote UMC800.