Mounting and Wiring
Remote Access

50

UMC800 Controller Installation and User Guide

Release F

4/01

SixNet VT-MODEM Industrial External Modem

Step

Action

1

Connect the modem to a PC. If your PC’s RS232 port has a 25 pin connector, use a DB-9
male to DB-25 female modem cable. If your PC’s RS232 port has a 9 pin connector, use a
DB-9 male to DB-9 female RS232 cable.

2

Connect power to the modem. You will need to supply an external power supply with a DC
voltage between 10 and 30 VDC.

3

Power-up the modem.

4

Run a serial communication port program such as Hyperterminal.

5

Within the communication program, select the port to which the modem is connected.

6

Configure the port to these settings:

baud rate = 9600
data bits = 8
parity = none
stop bits = 1
flow control = none

7

In the program’s terminal window, type in the letters “AT E1 Q0” followed by the enter key. The
modem should give an OK response.

8

Enter the following command string:

AT &Y0 &C0 &D0 &R1 &S0 &K0 S0=1

Modem should respond with OK.

9

Enter the following command string:

AT E0 Q1 &W0

Modem will not respond.

10

Power down the modem and disconnect it from the PC.

11

Connect the modem to the RS232 port of the UMC800 using a DB-9 male to DB-9 male
modem cable. Null modem cable may not work.

12

Connect the modem to a telephone jack.

13

Power-up the modem and the UMC800.

14

On a remote computer, run Control Builder software.

15

Setup Control Builder to dial the UMC800.

16

Verify that communications is established with the remote UMC800.