Maintenance, Overview – Honeywell UMC800 User Manual

Page 71

Advertising
background image

Maintenance

Overview

Release F

UMC800 Controller Installation and User Guide

63

4/01

Maintenance

Overview

This section covers procedures in the maintenance, calibration and replacement of the controller and its
components.

Maintenance to the controller consists of the following procedures:

Routine maintenance

Calibration of I/O modules.

(The backplane is factory calibrated only.)

Field replacement of controller components

Warranty

Warranty repair is by board replacement.

Non-warranty service provides for field repair at the board level with option to return to factory for
repair.

Servicing

The power supply, CPU, and all I/O modules plug into the backplane for easy removal and replacement.
The I/O modules can be replaced without removal of the field wiring from the terminal screws.

The battery is accessible for easy replacement while the controller file is powered and operational to
prevent loss of configuration data.

CAUTION

TO PRESERVE THE CONTROLLER CONFIGURATION PRIOR TO PERFORMING ANY
REPLACEMENT PROCEDURES OR REMOVING POWER TO THE CONTROLLER:

Be certain that the LoBatt LED is OFF. (MEMORY – LOW BATTERY diagnostic is not

active.)

Force a cold start of the controller by setting the manual mode switch on the controller to

PROGRAM and then to RUN and allow the controller to complete its start up sequence.
Controller configuration files will be backed up to the flash PROM on the CPU

WARNING – SHOCK HAZARD

Troubleshooting may require access to hazardous live circuits, and should only be
performed by qualified service personnel. More than one switch may be required to de-
energize unit before servicing.