Replacing the battery

A lithium battery is used as a keep alive voltage for the volatile memory (RAM) that contains the controller
configuration. The battery is installed in a compartment on the CPU module. Follow the steps in the table
below to replace the CPU battery.

CAUTION

The battery used in this device may present a risk of fire or chemical burn if mistreated. Do not
recharge, disassemble, heat above 212 °F (100 °C), or incinerate. Replace battery with
Tadiran TL-5101/SBP only. Use of another battery may present a risk of fire or explosion.

Step

Action

1

Locate the battery and the battery compartment location on the CPU module. See Figure 36.

2

Using a Phillips-head screwdriver, loosen the screw and remove the battery compartment
cover.

3

For the standard CPU module –

Using a screwdriver, insert it through the screw hole on the front and carefully pry the
battery out of its holder. Carefully remove battery from the holder.

For the CPU module option –

The battery holder is contained on the battery compartment cover. See figure. Carefully
remove battery from the holder.

- +

Battery Compartment Cover

Battery

4

Observing the correct polarity, insert a new battery into the holder.

5

Verify that the LoBATT LED is off.

If LED is lit, the battery may installed incorrectly. Check polarity of battery and reinstall, if
necessary.

6

Replace the compartment cover and secure with the screw.

NOTE:

If controller power is restored and the battery-backed RAM has failed, field calibration of the AI

modules must be performed if greater than 0.1% accuracy is required.