Diagnostics and Troubleshooting

Fault Detection and Troubleclearing

Release F

UMC800 Controller Installation and User Guide

85

4/01

Controller

Diagnostic Summary

(In the User Utility and Operator

Interface)

Controller

LED on CPU

Fault Detection / Troubleclearing

Menu

Item

Status

Possible Cause

Controller Action

User Action

RTC

BATTERY
FAILURE

POWER
LED flashes
8 times

RTC battery failed
on power-up

Time and date is
set to 00:00:00,
January 1, 1970.

1.

If Lo BAT LED
is off, cycle
power.

2.

If Lo BAT LED
is on, replace
battery and
cycle power.

RTC

PROGRAMMING
FAILURE

POWER
LED flashes
7 times

RTC failed to
program

Time and date is
set to 00:00:00,
January 1, 1970.

1.

Program RTC.

2.

Cycle power.

3.

Replace CPU.

4.

Replace
boards in
backplane.

5.

Replace
backplane.

RTC

READ FAILURE

POWER
LED flashes
7 times

Unable to read
RTC

Time and date is
set to 00:00:00,
January 1, 1970.

1.

Program RTC.

2.

Cycle power.

3.

Replace CPU.

4.

Replace
boards in
backplane.

5.

Replace
backplane.

I/O

GOOD

none

I/O

MODULE
ERROR

N/A

One of the I/O
board diagnostics
failed.

N/A

Access the I/O
MODULE
DIAGNOSTICS
display.

I/O

BAD BACKPAN

POWER
LED flashes
9 times.

Bad backplane
EEPROM

Analog inputs use
default coefficients.

1.

Cycle power.

2.

Replace
backplane
board.

I/O

BAD BACKPAN
ID

POWER
LED flashes
9 times.

Incompatible
backplane board

Analog inputs use
default coefficients.

1.

Cycle power.

2.

Replace
backplane
board.