Diagnostics and Troubleshooting
Fault Detection and Troubleclearing

86

UMC800 Controller Installation and User Guide

Release F

4/01

Controller

Diagnostic Summary

(In the User Utility and Operator

Interface)

Controller

LED on CPU

Fault Detection / Troubleclearing

Menu

Item

Status

Possible Cause

Controller Action

User Action

COMM A

GOOD

none

COMM A

BOARD
FAILURE

POWER
LED flashes
13 times.

The COMM A port
hardware has a
serious failure.

Executes normally.

Replace Comm
board.

COMM A

BOARD NOT
FOUND

POWER
LED flashes
13 times

The main CPU
board has a non-
default address
and no COMM
port installed.

Executes normally.

Install CPU with
optional RS 485
communications
(if not installed)
or set COMM A
station address to
255.

COMM B

GOOD

none

COMM B

BOARD
FAILURE

POWER
LED flashes
13 times.

The COMM B port
hardware has a
serious failure.

Executes normally.
All Modbus read
block outputs are
frozen at their last
read values.

Replace CPU.

COMM B

BOARD NOT
FOUND

POWER
LED flashes
13 times

The control file
configuration
requires a master
port and no Comm
Port is installed.

Executes normally.
All Modbus read
block outputs are
frozen at their last
read values.

Install Comm
Board or
download a
configuration that
has no Modbus
slave blocks

PANEL
(OI)

NORMAL

none