Diagnostics and Troubleshooting

Fault Detection and Troubleclearing

Release F

UMC800 Controller Installation and User Guide

87

4/01

Fault detection and troubleclearing

Table 21 describes the status messages that appear on the I/O Module Diagnostics displays in the user
utility and operator interface, as well as the status indications of the POWER LED located on the controller
CPU module.

Table 21 Details of the I/O module diagnostics display

I/O Module

Diagnostics

(In The User Utility and

Operator Interface)

Controller

LED on CPU

Fault Detection / Troubleclearing

Menu

Item

Status

Possible Cause

Controller Action

User Action

MODULE
1 through
MODULE
16

GOOD

MODULE
1 through
MODULE
16

HI CJ
TEMPERATURE

POWER
LED flashes
10 times

High cold junction
temperature on AI
module.

Executes normally.

1.

Improve
ventilation to
rack.

2.

Replace AI
module

MODULE
1 through
MODULE
16

WRONG
MODULE

POWER
LED flashes
11 times

The module does
not agree with the
module required
for the control
strategy.

These function
block types do the
following:

AI – sets its output
to failsafe

DI – sets its output
to OFF

1.

Replace
module.

2.

Check
configuration.

MODULE
1 through
MODULE
16

NO MODULE

POWER
LED flashes
11 times.

No module found
in the slot that
requires a module
for the control
strategy.

These function
block types do the
following:

AI – sets its output
to failsafe

DI – sets its output
to OFF

1.

Install the
correct type of
module.

2.

Check
configuration.