Wiring NPB-PWR-UN-H input power and earth ground.

1. Remove power from the AC circuit being wired to the NPB-PWR-UN-H—see previous .

2. Remove the NPB-PWR-UN-H cover.

To do this, press in the four tabs on both ends of the unit, and lift the cover off. If the WEB/CP-700 is plugged into the unit,

you may need to slide it away to get to the cover tabs.

3. Connect the supplied earth grounding wire to a nearby grounding point. See Fig. 7.

4. Make AC circuit connections line (mains) and neutral to the terminals labeled “INPUT PWR.”

5. Replace the cover on the NPB-PWR-UN-H.

Make sure all modules in the mounted assembly are firmly connected together and secured.

CAUTION

Do not energize the AC circuit wired to the NPB-PWR-UN-H until all other controller mounting and wiring is

completed. See Power Up and Initial Checkout, page 19.

Power and ground is also provided in wiring to remote I/O modules through the 6-position connector. However, note for

each

remote I/O module, you should also connect its earth ground spade lug to earth ground at that module’s location.

NPB-WPM-US (WALL MOUNT AC ADAPTER)

You can order and adapt a wall mount AC adapter (model NPB-WPM-US) to power

only the WEB/CP-700 controller. To use the

adapter, you must cut off its “barrel plug” end, then wire the two leads into the top positions of the 6-position end connector plug,

observing proper + and – polarity.

NOTE: I/O modules cannot be powered by that NPB-WPM-US adapter.

Before plugging the wired connector plug into the WEB/CP-700, check for 15Vdc at the proper polarity using a

multimeter (see Fig. 8).

Fig. 8. Adapting a NPB-WPM-US wall mount AC adapter to power the WEB/CP-700.

Do not power the controller until all other mounting and wiring is completed. See Power Up and Initial Checkout, page 19.

+

-

+

-

15.1

V

DC

Positive (+) Wire with White Stripe

Cut off barrel plug

NPB-WPM-US

Check with multimeter before

6-position

end

connector

plug