Contact Inputs

Three contact inputs (CIs) are available on a 6-position connector next to the 2-position external battery connector. CIs are

typically used to monitor normally-closed (N.C.) alarm contacts, if available on a UPS and/or the “door tamper” switch of an

enclosure. These CIs are

unsupervised—no end-of-line resistors are required. Fig. 9 shows example wiring to all three CIs of

the WEB/CP-700.

Fig. 9. Contact Input wiring to WEB/CP-700

BB

+

UP

S

A

C

UP

S

B

A

TT

GN

D

GN

D

GN

D

DO

O

R

T

M

P

BB –

Tamper

switch

UPS Alarm Contacts

Power Fail (if available)

Low Battery (if available)

WEB/CP-700