Replacement parts, Non-replaceable parts, Standard replacement parts – Honeywell NIAGARA WEB-700 User Manual

Page 23: New replacement unit, Replacement parts 23, Non-replaceable parts 23, Standard replacement parts 23, New replacement unit 23, Warning

Advertising
background image

WEB-700 WEB-700-O CP-700

23

95-7776—03

NOTE: Dispose of the used NiMH battery properly.

4. Unplug the NiMH battery from the main board connector (see Fig. 12).

5. Using a 1/4" (6mm) nutdriver, unfasten and retain the two kep nuts that secure the metal battery bracket to the shield, and

remove the shield and battery pack.

6. Put the replacement battery into the metal shield, and refasten back into place on the shield, using the two kep nuts. Hand

tighten with a nutdriver.

7. Plug the battery connector plug of the replacement battery into the NiMH battery connector on the main board of the WEB/

CP-700. The connector is keyed—you cannot plug the battery in reversed.

8. Replace the cover.

9. Restore power to the WEB/CP-700 and verify normal operation.

BATTERY DISPOSAL

Please dispose of the used NiMH battery in accordance with local, state, and federal regulations.

WARNING

Do not incinerate or mutilate the battery, as this may cause it to burst or release toxic materials.

If regulations specify returning the old battery to a recycling center, but no acceptable recycling center can be found, please

return the old NiMH battery pack to Tridium for proper disposal.

REPLACEMENT PARTS

Servicing the WEB/CP-700 may call for replacement parts. There are three categories of parts:

Non-replaceable Parts

Standard Replacement Parts

New Replacement Unit

Non-replaceable Parts

FUSE

The WEB/CP-700 contains a non-user replaceable 2.5A slow-blow fuse, soldered on the main circuit board. This fuse provides

protection from internal shorts or connection to incorrect power supplies. If the fuse circuitry is suspect, contact your regional

Tridium office for technical support. See “Returning a Defective Unit” on page 25.

Standard Replacement Parts

MEMORY

Standard replacement parts are listed in Table 5, and can be ordered from stock without restriction. Standard replacement parts

cannot be returned for credit and should be disposed of in an appropriate manner.

New Replacement Unit

To replace an entire unit, order and install a

new WEB/CP-700. If the faulty WEB/CP-700 is still in warranty, you can receive

credit by returning it to Tridium. Be sure to contact Tridium for a return authorization (RA) number before shipping an item for

return credit. See Returning a Defective Unit, page 25, for more details.

NOTE: Before ordering a new WEB/CP-700, it is strongly recommended that you contact your normal technical support

resource to eliminate the possibility of a software issue or mis-configuration problem.

Table 5. Standard replacement parts for a WEB/CP-700.

Part Number

Description

NPB-BATT-7

NiMH Battery Pack—see Required NiMH Battery Maintenance, page 22

NPM-1GB

1 GB DDR-2 333MHz SODIMM memory module (upgrade)

H11696

Hardware Bag for WEB/CP-700, containing screw terminal connector plugs (two 6-position,

one 2-position, earth grounding wire).

712BNP

SLA 12V 7AH External backup battery.

Advertising