background image

WEB-700 WEB-700-O CP-700

21

95-7776—03

ABOUT LEDS

The WEB/CP-700 provides a number of LEDs on its main board. Only the Status and Heartbeat LEDs are visible on the cover.

Checking other LEDs requires first removing the cover.

LEDs include the following types:

Status

Heartbeat

Debug

Ethernet Ports

For the location of LEDs on the main board, see Fig. 5, page 10.

Status

The green “STATUS” LED is located on the cover. On the main board, it is also the green “SYSOK” LED next to the “HBEAT”

LED—both are found near the Ethernet connector housing. The status LED should remain lit whenever the WEB/CP-700 is

powered, or else be blinking during the boot sequence. If the status LED does not light while power is applied, contact System

Engineering for technical support.

Heartbeat

The yellow heartbeat “HBEAT” LED is located on the cover, as well as on the main board next to the “SYSOK” Status LED. The

heartbeat LED blinks about once per second. If the heartbeat LED stays

on constantly, does not light, or blinks very fast (more

than once per second), contact your local distributor for technical support.

Debug

The yellow “DEBUG” LED is located on the main board near the Ethernet connector housing, and remains lit whenever the WEB/

CP-700 has been rebooted with the “serial mode select” jumper in the “serial shell” position (see Fig. 5, page 10). This indicates

that the DB-9 RS-232 port is operating in serial shell mode.

Ethernet Ports

Two LEDs for each of the two LAN ports are provided on the back of the metal LAN connector housing, and operate as follows.

The left-side

green “activity” LED indicates activity on that port as follows:

Off — No Ethernet link is made

On — Ethernet link is present, but no activity on the LAN

Blinking — Ethernet link is present with data activity on the LAN.

The right-side

yellow “speed” LED Indicates Ethernet connection speed, as either:

OFF - "Fast Ethernet"/"Ethernet" (100 Mbps/10 Mbps).

ON - "Gigabit Ethernet" speed (1000 Mbps).

MAINTAINING THE WEB/CP-700

This section provides information on the following topics:

Cleaning

Required NiMH Battery Maintenance

Replacement Parts

Replacing the WEB/CP-700

Returning a Defective Unit

Cleaning

If dust or metal filings are present inside the unit, clean with vacuum or compressed air. Otherwise, no cleaning inside the unit is

required. If the cover becomes dirty, you can wipe it with a damp cloth and mild detergent.