Rf b, Election, Figure 5-2 menu map to rf baud rate setting – Honeywell ISM BAND XYR 5000 LINE User Manual

Page 27: Rf baud rate selection, 2 rf baud rate selection

Advertising
background image

5.2 RF Baud Rate Selection

The RF Baud Rate refers to the speed at which the Base Radio and Transmitters
communicate. There are three selectable settings with the quickest update times and
longest communication ranges listed below:

4.8K — Rate of 4.8 Kbaud (Update every 20 seconds)

— Range of 3000 ft (Line of Sight)

19.2K — Rate of 19.2 Kbaud (Update every 5 seconds)

— Range of 2000 ft to 2500 ft (Line of Sight)

76.8K — Rate of 76.8 Kbaud (Update every 1 second)

— Range of 500 ft to 750 ft (Line of Sight)

A faster RF Baud Rate will allow you to transmit more information in a certain period of
time, but it will also limit your range. If you need more distance out of your Transmitters or
are encountering difficulties by frequently losing communications, then select a slower
baud rate or switch to a high gain antenna.

Note If you change the baud rate of the Base Radio, you must also change the baud rate
of all other Transmitters that are communicating with that Base Radio.

Follow the Base Radio menu map shown in Figure 5-2 to configure the RF Baud Rate.
The factory default is the 19.2K Baud Rate.

Figure 5-2 Menu Map to RF Baud Rate Setting