5.3 High RF ID Setting

The Base Radio uses this parameter along with the RF CHAN and BAUD RT parameters
to set up communication with Transmitters. This setting should be a number between 1
and 100 corresponding to the Transmitter with the highest RFID on the system. Any
Transmitter with an RFID set above the HI RFID setting will not communicate with the
Base Radio. The factory default is 001.

Figure 5-3 High RFID Setting

Note that the Output Modules with firmware prior to 1.7 (purchased before May 2006) will
not work with the Base Radio when the HI RFID setting is set above 50.