Figure 6-2 menu map to modbus device id setting – Honeywell ISM BAND XYR 5000 LINE User Manual

Page 31

Advertising
background image

Base Radio with Modbus device ID 001

Transmitter with RF ID 1 is found at Modbus device ID 002
Transmitter with RF ID 2 is found at Modbus device ID 003
Transmitter with RF ID 3 is found at Modbus device ID 004

Base Radio with Modbus device ID 101

Transmitter with RF ID 1 is found at Modbus device ID 102
Transmitter with RF ID 2 is found at Modbus device ID 103
Transmitter with RF ID 3 is found at Modbus device ID 104

More detail about the registers at each address, and their meaning, can be found in the
Modbus Communications Protocol section.

Once you have determined the Modbus Device ID you wish to use, follow the Base Radio
menu map shown in Figure 6-2 to configure the device ID. The factory default is 001:

Figure 6-2 Menu Map to Modbus Device ID Setting

Note The Base Radio provides different Device ID modes in order to support a wide
range of Modbus equipment.

In the Register Mapping Mode the data for the Base Radio and all Transmitters are
located under a single device ID. This ID may be any allowable Modbus address between
1 and 247 that doesn’t conflict with an address of existing device or Modbus network.

In the Device ID Mapping Mode each Transmitter is given its own unique ID and
registers. The Transmitter ID is equal to the value of the Base Radio ID added to the
Transmitters RF ID.

Note Make sure that the HI RF ID setting has been configured properly or the Modbus
addressing scheme could be affected.

To properly set the HI RF ID setting see Section 4.2.