00005 + (RF ID * 10)

Primary Sensor Value

00006 + (RF ID * 10)

Primary Sensor Value

32-Bit IEEE
Floating Point

00007 + (RF ID * 10)

Secondary Sensor Value

00008 + (RF ID * 10)

Secondary Sensor Value

32-Bit IEEE
Floating Point

00009 + (RF ID * 10)

Tertiary Sensor Value

00010 + (RF ID * 10)

Tertiary Sensor Value

32-Bit IEEE
Floating Point

Note If you have purchased any Wireless Differential Pressure Transmitters, please
see the User Guide for specific Modbus holding register differences from those listed in
the following sections.

6.5.3 Transmitter Device Type Holding Registers

The following are possible values for the Device Type holding registers. Note that the
register is a 32-bit floating point value for Transmitters.

Value

Device Type

0 Acoustic Monitor Transmitter
1 RTD Transmitter
2 Pressure Transmitter
3 Dual 0-10V Input Transmitter
4 Dual 4-20mA Input Transmitter
5 Thermocouple

Transmitter

6 Reserved
7 Level Sensor Transmitter
8 Split RTD Transmitter
9 Split Pressure Transmitter

10 Split Dual Thermocouple Transmitter
11 Differential Pressure Transmitter (100 IN. H20)
12 Split Differential Pressure Transmitter (100 IN. H20)
13 Differential Pressure Transmitter (300 IN. H20)
14 Split Differential Pressure Transmitter (300 IN. H20)
15 Differential Pressure Transmitter (25 PSID)
16 Split Differential Pressure Transmitter (25 PSID)
17 Differential Pressure Transmitter (100 PSID)
18 Split Differential Pressure Transmitter (100 PSID)
19 Differential Pressure Transmitter (300 PSID)
20 Split Differential Pressure Transmitter (300 PSID)
21 Reserved
22 Reserved
23 Gauge and Submersible Level Transmitters
24 Split Gauge and Submersible Level Transmitters
25 Advanced

Development

26 Switch Input Transmitter
27 Switch Input Transmitter with Output Options

32