Chase, Firestop spacer, Termination installation – Hearth and Home Technologies NOVUS GNBC33 User Manual

Page 8: Novus b-vent installation instructions

Advertising
background image

34615 Rev G

8

12-02

NOVUS B-VENT INSTALLATION INSTRUCTIONS

3. FIRESTOP SPACER/VENT INSTALLATION

Frame an opening and install a firestop spacer

whenever the vent penetrates a ceiling floor area, as

shown in Figure 6. Frame the opening with the same

sized lumber as used in the ceiling/floor joist. Unless

the flue is offset, the hole should be directly above the

appliance. DO NOT pack insulation around the vent.

Assemble vent sections with three screws per joint.

WARNING - RISK OF FIRE!

Always maintain minimum clearances or greater

around the vent system. Do not pack air spaces with

insulation or other material. The flow of combustion

and ventilation air must not be obstructed.

WARNING!

The horizontal run of vent must have a 1/4” rise for

every 1 ft. of run towards the termination. Never al-

low the vent to run downward. This could cause high

temperatures and may present a fire hazard.

WARNING!

When vent sections exceeding three feet in length

are installed between an offset/return, structural sup-

port must be provided to reduce off-center loading

and prevent vent sections from separating at the vent

joints. Follow all B-vent manufacturer guidelines.

4. CHASE/TERMINATION INSTALLATION

Figure 7 and Table 1 specify minimum vent heights for

various pitched roofs. Vent sections may have to be cut

to a certain length.

These vent heights are necessary for safety and do not

ensure draft-free operation. Trees, buildings, adjoining

roof lines, adverse conditions, etc., may create a need

for a taller vent should down drafting occur.

Figure 6

Installing the Firestop Spacer

Advertising
This manual is related to the following products: