F76S WATER FILTERS AND MV876B AUTOMATIC-BACKWASH CONTROLS

62-3015—4

4

PLANNING THE INSTALLATION

The F76S should be sized based on the required flow rate and
the resulting pressure drop across the filter. As a guideline for
most applications, the F76S should be sized to avoid pressure
drops exceeding 3 psi.

EXAMPLE:What size F76S is required to provide a flow

rate of 30 gpm? Reading across Table 1 at
3 psi pressure drop, a 1 in. filter can provide 31
gpm without exceeding 3 psi pressure drop.

An increased pressure drop across the filter results when
higher velocities are maintained to increase the capacity
through any given size filter. Severe pressure drops will be
encountered as capacity approaches that of the pipe size. To
ensure the backwash cycle operates properly and cleaning
action is not reduced, follow all recommendations in Fig. 2.
Refer to Fig. 2a for an ideal installation.

NOTE:

All filter installations are different. The size, type, and
amount of dirt and debris and the flow rate must
always be considered when choosing a screen and
deciding to install multiple F76 Water Filters in parallel.

Fig. 2. Installation recommendations.

100

150

50

0

200

Honeywell
Braukmann

M16488

Fig. 2a. Ideal F76S installation. A funnel

mounted directly under the backwash

port is the best installation layout.

Fig. 2b. Ensure the inlet pipe is not

downsized. Do not use 1/4 or 3/8 inch

tubing on 1/2 or 3/4 inch models.

Fig. 2c. Ensure the backwash outlet

pipe is not downsized, long, or

crimped. Instead, install a short

oversized pipe on the backwash outlet.

Do not use a low capacity solenoid

valve to automate the backwash cycle.

100

150

50

0

200

Honeywell
Braukmann

M16489

100

150

50

0

200

Honeywell
Brau

kma

nn

M16490

100

150

50

0

200

Honeywell
Braukmann

M16491

100

150

50

0

200

Honeywell
Braukmann

M16492

M16478

100

150

50

0

200

Honeywell
Braukmann

Fig. 2d. Ensure the backwash outlet is

not raised above the F76S. If the

backwash outlet must be raised above

the F76S, increase inlet pressure 5 psi

for every 10 feet that it is raised.

Fig. 2e. Ensure the F76S is not used

with an undersized pump. An

undersized pump may not provide

proper pressure or flow.

Fig. 2f. Ensure the F76S is not

installed in a bypass across a pump.