Installation Guide

69-299—0



advaNCEd CONfiguraTiON

Table 5. Advanced Configuration.

Menu Name

Menu Title (LCD

top line)

Menu Options (LCD bottom

line; defaults in bold)

Menu option description

Notes:

Heat Fan

HEAT FAN

CONTROL

[HVAC] PANEL

Fan control by HVAC

In heat mode, fan controlled by HVAC or turned

on by panel in call for heat.

HVAC [PANEL]

Fan control by Panel

Stage 2 Timer

STAGE 2 TIMER

[5 MIN] > – < [60 MIN]
[5 MIN] >

5 minutes–60 minutes

Number of minutes to delay before engaging

second stage.

Purge Timer

PURGE TIME

[2] 3.5 5 MIN

2.0 minutes

Number of minutes panel will purge following

call for heat or cool.

2 [3.5] 5 MIN

3.5 minutes

2 3.5 [5] MIN

5.0 minutes

Purge Fan

FAN IN PURGE

[HVAC] PANEL

Fan control by HVAC

Fan controlled by HVAC or panel during purge.

HVAC [PANEL]

Fan control by Panel

Purge Dampers

PURGE DAMPERS [UNCHANGD] OPEN

Dampers Unchanged

Damper position unchanged or all dampers

open during purge.

UNCHANGD [OPEN]

Dampers All Open

Auto Changeover Delay CHANGEOVER

DELAY

[15] 20 30 MIN

15 minutes auto changeover timer

Number of minutes to delay auto changeover

when one zone is calling for heat and another

is calling for cooling.

15 [20] 30 MIN

20 minutes auto changeover timer

15 20 [30] MIN

30 minutes auto changeover timer

DATS Enabled

DISCHARGE

SENSOR

[NO] YES

Disabled

Enables or disables DATS. If Disabled, the

Multistage DATS Inhibit setting is Disabled.

NO [YES]

Enabled

DATS High Limit

DAT HIGH LIMIT

[110 F] > – < [180 F]

< [160 F] >

110 deg F–180 deg F

High temperature limit.

DATS Low Limit

DAT LOW LIMIT

[30 F] > – < [60 F]
< [40 F] >

30 deg F–60 deg F

Low temperature limit.

OT Temp Enabled

OT SENSOR

[NO] YES

Disabled

Enables or disables outdoor temperature

sensor. If Disabled, the Multistage OT Temp

Lockout setting is Disabled.

NO [YES]

Enabled

OT Trip Point for

Multistage Lockout

OT LOCKOUT

TEMP

[0 F] > – < [50 F]
< [50 F] >

0 deg F–50 deg F

Above this temperature 2nd stage heat is

locked out.

Multistage DATS Inhibit DAT MSTG INHIBIT NO [YES]

Enabled

Allow panel to downstage multistage equip-

ment when near DATS high or low limit.

[NO] YES

Disabled

LCD Contrast Adjust

LCD CONTRAST

[1] > – < [10]
< [5] >

Contrast value 1–10

Sets LCD display contrast for ease of viewing.

Lowest contrast is 1, highest contrast is 10.

Save Changes

SAVE CHANGES?

[NO] YES

Disabled

Saves or rejects the configuration settings.

NO [YES]

Enabled

Reload Defaults

RELOAD

DEFAULTS?

[NO] YES

Disabled

Restores the panel's default configuration

settings.

NO [YES]

Enabled

Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 7
for instructions on using these buttons.

Press the Mode button until the Wireless LED lights
up. The TrueZONE must be configured for wireless
devices to select Wireless mode.

4

CONNECT WirElEss dEviCEs

HOME

MODE

BACK

NEXT

CONFIG

CHECK OUT

ADJUST SETTING

M28194

WIRELESS

Press Next to add devices.
While the display alternates the Press Connect and
Exit screens, push the Connect button(s) on the wire-
less device(s).
-OR-
Follow the instructions that came with the wireless
device(s).
Press Next to exit.

Fig. 15