HZ322 TrueZONE



69-299—0

WiriNg

Follow these steps for wiring all systems. However, wiring will vary depending on equipment. For conventional sys-
tems, refer to page 5. For heat pump systems, see page 6.
Wiring must comply with applicable codes, ordinances, and regulations. Use the following wiring diagrams to wire
the zone panel to the thermostats and dampers.

The HZ322 offers many innovations for wire management and organization: wires can be run
behind the panel, through wire channels on its sides, and must be attached to a wiring anchor
with a cable tie.

M24743

Install thermostats using instructions provided with thermostats.
Connect thermostat to zone panel. To connect wire to the panel, strip
approximately 1/4 in. of insulation and push wire into terminal. To
release wire, press the button on top of the terminal.
In retrofit applications, trim end of wire if not straight.

3

Install dampers using instructions provided with dampers.
Connect dampers to zone panel.
NOTE: Multiple dampers can be wired in parallel.

4

M28023

Rc

R

C

W

W2

Y

Y2

G

M1

M4

M6

R

C

W1/E

W2

Y1

Y2

G

O/B

L

ZONE

3

DAMPE

R

THERMOST

AT

CAUTION: Voltage Hazard.
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
Wire entire panel before applying transformer power.

Fig. 4

Fig. 5

Fig. 6

M24920

ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED

ZONE

3

DAMPER

M1

M4

M6

R

ZONE

1

DAMPER

RRD OR MARD DAMPER POWER-OPEN POWER-CLOSED

M4 OPEN

M6 CLOSED

M1 COMMON

ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED

ZONE

2

DAMPER