R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS

68-0105—2

8

Fig. 10. Converting TRADELINE® R8182D,H to replace other controls.

M4526

USING THE TRADELINE® R8182D
TO REPLACE R8182F:

1. REMOVE BLUE WIRE FROM
THIS TERMINAL AND INSULATE
END TO PREVENT CONTACT.

2. REMOVE OTHER BLUE WIRE
FROM THIS TERMINAL AND
CONNECT AS SHOWN BELOW.

3. CONNECT CIRCULATOR TO
ZC AND C2.

USING THE TRADELINE® R8182D
TO REPLACE R8182B,E OR
WHITE RODGERS 6C92:

1. REMOVE WHITE ABD BLACK
LEADS FROM THEIR TERMINAL
AND CONNECT WITH A
SODDERLESS CONNECTOR.

TO USE TRADELINE® R8182H
TO REPLACE R8182J:

1. REMOVE RED AND WHITE
LEADS FROM THEIR TERMINALS
AND CONNECT WITH A
SOLDERLESS CONNECTOR.

COMPLETED WIRING
TO REPLACE
R8182B,E AND
WHITE RODGERS 6C92

COMPLETED
WIRING TO
REPLACE
R8182C,F

L

O

H

I

BLUE

WHITE

BLACK

YELLOW

L

O

H

I

BLUE

BLUE

BLACK
OR RED

YELLOW