R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS

13

68-0105—2

R8182J

The burner and circulator operate whenever the thermostat

calls for heat. Relay 2K pulls in. When the cadmium sulfide

flame detector sees flame, the safety switch heater circuit is

bypassed, and 2K is held in through 2K1. If temperature rises

to a high limit setpoint, R to B breaks, shutting off the burner.

The circulator continues operation under direction of the

thermostat. See Fig. 15, 16, 17 and 19.

Multizone Control

In all multizone applications, a call for heat in any zone

energizes the safety switch circuit and relay 2K pulls in. If the

burner ignites within the safety switch timing, the cadmium

sulfide flame detector sees flame and the safety switch heater

is bypassed.

In all multizone applications with R8182D and H, the low limit

control in the Aquastat® limit acts independently to turn on the

main burner on a drop in water temperature. When R to B (low

limit) is made, relay 2K pulls in to turn on the main burner, the

same as for single-zone application.

Zone Circulator Control with R8182D,H

The relay for each zone is connected to the Aquastat® limit

through terminals ZC and ZR. The R845 Relay and

thermostat for each zone can energize the zone circulator

through ZC only if R to W in the Aquastat® limit is made. If

R to B (high limit) is made, the zone thermostat energizes the

burner through ZR.

Zone Circulator Control with R8182E,J

The relay for each zone is connected to the Aquastat® limit

through terminals ZC and ZR. The R845A Relay and

thermostat in each zone can energize the zone circulator

through ZC on a call for heat. If R to B (high limit) is made, the

zone thermostat energizes the burner through ZR.

Zone Valve Control with R8182

The valve for each zone is connected to the Aquastat® limit

by wiring end switches on the zone valve to T-T on the R8182.

On a call for heat from any zone, the R8182 operates the

same as for single zone applications.

Fig. 18. R8182D,H Aquastat® limit switching.

Fig. 19. R8182E,J Aquastat® limit switching.

LOW LIMIT
AND
CIRCULATOR
SETTING

HIGH LIMIT
SETTING

SWITCH BREAKS ON
TEMPERATURE RISE.
BURNER TURNS OFF.
CIRCULATOR OPERATES
ON A CALL FOR HEAT.

SWITCH MAKES ON
TEMPERATURE FALL.
BURNER OPERATES ON A
CALL FOR HEAT.

SWITCH MAKES R-W
AND BREAKS R-B ON
TEMPERATURE RISE.

SWITCH MAKES R-B AND
BREAKS R-W ON
TEMPERATURE FALL.
BURNER IS ON TO
MAINTAIN MINIMUM
WATER TEMPERATURE.
CIRCULATOR IS OFF.

M1523

SWITCH MAKES R-W
AND BREAKS R-B ON
TEMPERATURE RISE.

WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER
SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING
FOR HEAT).

1

1

R-B MAKES ON
TEMPERATURE FALL.
BURNER AND
CIRCULATOR OPERATE
ON A CALL FOR HEAT.

180

°

F (82

°

C)

240

°

F (116

°

C)

M1510

R-B BREAKS ON
TEMPERATURE RISE.
BURNER TURNS OFF.
CIRCULATOR OPERATES
ON A CALL FOR HEAT.

HIGH LIMIT
SETTING

15

°

F (8

°

C)

DIFFERENTIAL