HE225A,B AND HE265A,B BYPASS FLOW-THROUGH HUMIDIFIER

68-0244

6

Table 5. Recommended Convertible Humidity Control Settings.

Humidity Level

Recommended Adjustment

Insufficient humidity

Increase the frost factor dial by one setting.

Condensation on windows

Decrease the frost factor dial by one setting.

At Outside Temperature

Recommended Setting

At Outside Temperature

Recommended Setting

-20°F (-29°C)

15

+10°F (-12°C)

30

-10°F (-23°C)

20

+20°F (-7°C)

35

0°F (-18°C)

25

Above 20°F (-7°C)

40

Table 6. Recommended Frost Factor Settings.

OPERATION

The HE225A,B and HE265A,B Humidifiers use the principle
that vapor (evaporated water) is created when warm air blows
over a water soaked area. As the vapor circulates, the relative
humidity rises.

The humidity control monitors the relative humidity and
activates the humidifier accordingly. The humidifier has a
water supply that disburses water over an antimicrobial
humidifier pad. The warm dry air from the furnace passes
over the humidifier pad and collects moisture and them
circulates it through the house.

Humidified air feels warmer and more comfortable so the
homeowner may be able to lower the thermostat heating
setpoint and save money on heating fuel bills. The end result
is that the humidifier gives the homeowner a comfortable
environment that is also energy efficient.

MAINTENANCE

A regular maintenance program prolongs the life of the
humidifier and provides a more comfortable environment.
Either hard or soft water can be used in the humidifier.
Frequency of cleaning depends on the condition of the water.

CAUTION

Voltage Hazard.
Can cause electrical shock and equipment
damage.
Disconnect power supply before installing or
servicing.

IMPORTANT

Never oil any part of the humidifier.

Every 1 to 3 Months
(Depending on Water Quality)

Use the following procedure to clean the humidifier:

1. Disconnect the power and turn off the humidifier water

supply.

2. Remove the humidifier cover. See Fig. 5.

Fig. 5. Location of humidifier parts.

3. Remove the humidifier pad assembly from the

humidifier by grasping the tray and pulling it toward
you.

4. Pull one side of the humidifier pad assembly frame

toward you and remove the tray from the frame.

5. Gently pinch the water nozzle catches inward until the

water nozzle can be lifted off the tray.

6. Slide the antimicrobial humidifier pad out of the frame.
7. Carefully scrape any mineral deposits from the tray and

frame. Be sure the frame drain hole has nothing
blocking it.

M14672

WATER
FEED NOZZLE

FRAME

HUMIDIFIER
HOUSING

WATER
FEED TUBE

HUMIDIFIER
PAD ASSEMBLY

COVER

SIDEWALL

BY-PASS SIDEWALL