L8124A,C,E,L AND M AQUASTAT® RELAYS

7

95-6571—11

Fig. 11. L8124L multizone system with circulator connections and internal schematic.

OPERATION

High Limit Controller

The high limit opens and turns off the burner when the
water temperature reaches the setpoint. The high limit
automatically resets after the water temperature drops
past the setpoint and through the 10°F (6°C) differential.

WARNING

Explosion Hazard.
Can cause serious injury, death or equipment
damage.
Use this product only in systems with a pressure
relief valve.

Low Limit and Circulator Controllers

On a temperature rise, with the adjustable differential at
the minimum setting of 10°F (6°C), the burner circuit
(R-B) breaks and the circulator circuit (R-W) makes at
the control setpoint. On a temperature drop of 10°F (6°C)
below the setpoint, the R-B circuit makes and the R-W
circuit breaks. See Fig. 12.

At any differential setting greater than 10°F (6°C), the
R-B make temperature and the R-W break temperature
remain the same (control setting minus 10°F [6°C]). The
R-B break and R-W make temperature are the setpoint
temperature plus the difference between the differential
setting and 10°F (6°C).

EXAMPLE: Setpoint of 140°F (60°C), differential set
at 25°F (14°C). On a temperature rise, R-B breaks
and R-W makes at 155°F (68°C). On a temperature
fall, R-B makes and R-W breaks at 130°F (54°C).

Fig. 12. Relationship of setpoints and differential.

M8829

L1
(HOT)

L2

1

3

1

2

3

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.

CONTROL CASE MUST BE CONNECTED TO EARTH
GROUND. USE GROUNDING SCREW PROVIDED.

B1 IS 1/4 IN. TAB TERMINAL.

2

1

4

3

5

6

LOW VOLTAGE
THERMOSTAT
ZONE 1

ZONE 2
LOW VOLTAGE
THERMOSTAT

R845A RELAY ZONE 2

ZONE 2
CIRCULATOR

TO ADDITIONAL
R845A RELAYS
FOR OTHER ZONES

LINE VOLTAGE
OIL BURNER
RELAY OR
GAS VALVE

LINE VOLTAGE
CIRCULATOR
ZONE 1

B2
C2

C1

ZR

B1

R

B

HIGH
LIMIT

Z

1K1

B

R

W

LOW LIMIT/
CIRCULATOR

1K

2

1

G

T

TV

L8124L

1K2

ZC

LOW LIMIT
AND
CIRCULATOR
SETTING

HIGH LIMIT
SETTING

SWITCH BREAKS ON
TEMPERATURE RISE.
BURNER TURNS OFF.
CIRCULATOR OPERATES
ON A CALL FOR HEAT.

SWITCH MAKES ON
TEMPERATURE FALL.
BURNER OPERATES ON A
CALL FOR HEAT.

SWITCH MAKES R-W
AND BREAKS R-B ON
TEMPERATURE RISE.

SWITCH MAKES R-B AND
BREAKS R-W ON
TEMPERATURE FALL.
BURNER IS ON TO
MAINTAIN MINIMUM
WATER TEMPERATURE.
CIRCULATOR IS OFF.

M1523

SWITCH MAKES R-W
AND BREAKS R-B ON
TEMPERATURE RISE.

WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER
SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING
FOR HEAT).