3 changing default failsafe direction, Daughter pwa, Main pwa – Honeywell SMV 3000 User Manual

Page 109

Advertising
background image

1/99

SMV 3000 Transmitter User’s Manual

97

8.3

Changing Default Failsafe Direction,

Continued

Procedure, continued

Table 26

Cutting Failsafe Jumper, Continued

Step

Action

10

Turn ON transmitter power.

11

Perform Upload of the SMV database to the SCT.

12

Open the Status Tab Card. Read the gross and detailed status
messages of the transmitter. Verify that the status messages are the
same as recorded in Step 3.

Figure 27

Location of Failsafe Jumper on main PWA of Electronics Module.

Screw

Temperature

Input

Connector

Daughter PWA

Screw

PWA
Connector

PROM
Location

Flex Tape
Connector

Power
Connector

Write
Protect
Jumper

Screw

PWA
Connector

Main PWA

Plastic
Bracket

Failsafe
Jumper