4 diagnostic messages – Honeywell SMV 3000 User Manual

Page 141

Advertising
background image

1/99

SMV 3000 Transmitter User’s Manual

129

11.4

Diagnostic Messages,

Continued

Diagnostic Messages,
continued

Table 32

Non-Critical Status Diagnostic Message Table, continued

SMV Status

SCT Status Message SFC Display Message TDC Status Message

Possible Cause

What to Do

5-5

Input Mode PV2 (AP)

STATUS TAG ID.#

INPUT MODE PV2

INPUT MODE PV2

Transmitter is simulating input for
PV2.

Exit Input mode:

SCT – Press “Clear Input Mode”

button on the AP InCal tab.

SFC – Press [

SHIFT

], [

INPUT

], and

[

CLR

] keys.

5-6

Input Mode PV3 (Temp)

STATUS TAG ID.#

INPUT MODE PV3

INPUT MODE PV3

Transmitter is simulating input for
PV3.

Exit Input mode:

SCT – Press “Clear Input Mode”

button on the TEMP InCal tab.

SFC – Press [

SHIFT

], [

INPUT

], and

[

CLR

] keys.

5-7

Input Mode PV4 (Flow)

STATUS TAG ID.#

INPUT MODE PV4

INPUT MODE PV4

Transmitter is simulating input for
PV4.

Exit Input mode:

SCT – Press “Clear Input Mode”

button on the FLOW InCal tab.

SFC – Press [

SHIFT

], [

INPUT

], and

[

CLR

] keys.

2-0

Meter Body Sensor Over

Temperature

STATUS TAG ID.#

M.B. OVERTEMP

M.B. OVERTEMP

Sensor temperature is too high
(>125

°

C). Accuracy and life span

may decrease if it remains high.

Take steps to insulate meter body
from temperature source.

2-7

No DAC Temp Comp

Or

DAC Temperature

Compensation data is

corrupt

STATUS TAG ID.#

NO DAC TEMPCOMP

NO DAC TEMP COMP

Failed DAC.

Replace electronics module.