4 diagnostic messages – Honeywell SMV 3000 User Manual

Page 144

Advertising
background image

132

SMV 3000 Transmitter User’s Manual

1/99

11.4

Diagnostic Messages,

Continued

Diagnostic Messages,
continued

Table 33

Communication Status Message Table

SMV Status

SCT Status Message SFC Display Message TDC Status Message

Possible Cause

What to Do

-

Command Aborted

TAG NO.

COMM ABORTED

-

Communications aborted.

SFC – Pressed [

CLR

] key during

communications operation.

Retry aborted operation.

-

Communication Error

Upload failed

TAG NO.

END AROUND ERR

-

Communications unsuccessful.

Check loop wiring and
STC/SFC connections.

If error persists, replace
transmitter electronics module.

-

Download Failed

SAVE/RESTORE

RESTORE FAILED

-

Database restore or download
function failed due to a problem
with the current configuration or a
communications error.

Check transmitter and try again.

-

Invalid Response

TAG NO.

ILLEGAL RESPONSE

-

The transmitter did not respond
properly since the response was
not recognizable. The message
was probably corrupted by external
influences.

Transmitter sent illegal response to
SCT or SFC.

Try communicating again.

-

Illegal operation

URV 3 . TAG ID.

INVALID REQUEST

-

Requesting transmitter to correct or
set its URV to a value that results in
too small a span, or correct its LRV
or URV while in input or output
mode.

Check that correct URV
calibration pressure is being
applied to transmitter, or that
transmitter is not in input or
output mode.

SFC – Keystroke is not valid for
given transmitter.

Check that keystroke is
applicable for given transmitter.

SCT – The requested transaction is
not supported by the transmitter.

Make sure the device version is
compatible with the current
release of the SCT 3000.