SMV 3000 Transmitter User’s Manual

165

A.6

Operation Notes,

Continued

Database Mismatch
Parameters,
continued

If a mismatch is detected, only the slots (PVs) that have the mismatch will
have their PV value set to not a number (NAN) and their STATE
parameter on the Detail display will show DBCHANGE. Note that an
asterisk “*” will appear next to the PV number or Number of PVs on the
other slots to indicate that there is a problem.

DECONF Changes

A change in the DECONF parameter such as turning PV2, 3, or 4 ON,
which is equivalent to building a point for the given transmitter PV, can
only be downloaded from the Detail display for PV number 1. Enter
identical tag names for as many PVs as desired (sequentially, up to 4) and
then download from the master slot. If you try to download a DECONF
change from the Detail display for PV number 2, 3 or 4, you will get an
error message as shown in Figure A-7.

Figure A-7

Example of DECONF Download Error Message.

F101

SMV SLOT 2 - STATIC PRESS 03 UNIT 01

CONFIG PAGE

PVFORMAT 01
PVSRCOPT ALL
PVCLAMP

CLAMP

PVALDR ONE
PVALDEBEU 2.0000
INPTDIR REVERSE
LOCUTOFF -------

_________________ CONFIGURATION DATA ________________

PVCHAR LINEAR
SENSRTYP SPT_AP
PIUOTDCF OFF
BADPVPR LOW
PVHHPR NOACTION
PVHIPR NOACTION
PVLLPR NOACTION

PVLOPR NOACTION
PVROCPPR NOACTION
PVROCNPR NOACTION

______________ SMART TRANSMITTER DATA ______________

STITAG FT3011
SENSRTYP SPT_AP
PVCHAR LINEAR
CJTACT OFF
PIUOTDCF OFF
DECONF Pv_Db

PVRAW ------
URL ------
URV ------
LRV ------
LUL ------
STI_EU PSI

SECVAR ------
DAMPING 0.00000
SERIALNO
STISWVER
STATE LOADFAIL
COMMAND NONE

TRANSMITTER SCRATCH PAD:
TRANSMITTER STATUS : COMMAND ALLOWED ONLY ON FIRST

SLOT OF MULTIPLE PV XMTRS

2 OF 2

23 Jun 98 11:15:23 6

Message means you can only
initiate DECONF download
from Detail display for slot 1
or PV number 1.