SMV 3000 Transmitter User’s Manual

1/99

3.2

Considerations for SMV 3000 Transmitter,

Continued

RTD requirements

Use a two-, three-, or four-wire platinum 100 ohm (Pt100) Resistance
Temperature Detector with rated measurement range limits of –200 to
450 °C (–328 to 842 °F) per DIN 43760 standard (

α

= 0.00385

/

/

°

C)

as the input source for the process temperature PV.

Thermocouple
requirements

Use one of the thermocouple types listed in Table 4 as the input source for
the process temperature.

Table 4

Thermocouple Types for Process Temperature Sensor

Type

Rated Range Limits

Standard

°

C

°

F

E

0 to 1000

32 to 1832

IEC584.1

J

0 to 1200

32 to 2192

IEC584.1

K

–100 to 1250

–148 to 2282

IEC584.1

T

–100 to 400

–148 to 752

IEC584.1