4.5

Wiring SMV 3000 Transmitter,

Continued

Conduit seals and
Hazardous Location
Installations

Transmitters installed as explosionproof in a Class I, Division 1, Group A
Hazardous (Classified) Location in accordance with ANSI/NFPA 70, the
US National Electrical Code (NEC), require a “LISTED” explosionproof
seal to be installed in the conduit, within 18 inches of the transmitter.

Crouse-Hinds® type EYS/EYD or EYSX/EYDX are examples of
“LISTED” explosionproof seals that meets this requirement.

Transmitters installed as explosionproof in a Class I, Division 1, Group B,
C or D Hazardous (Classified) Locations do not require an explosionproof
seal to be installed in the conduit.

NOTE: Installation should conform to all national and local electrical
code requirements.

WARNING

When installed as explosionproof in a Division 1 Hazardous Location,
keep covers tight while the transmitter is energized. Disconnect power to
the transmitter in the non-hazardous area prior to removing end caps for
service.

When installed as nonincendive equipment in a Division 2 Hazardous
Location, disconnect power to the transmitter in the non-hazardous area,
or determine that the location is non-hazardous prior to disconnecting or
connecting the transmitter wires.