1/99

SMV 3000 Transmitter User’s Manual

51

6.5

General Configuration

PV Type

Selecting PVs for
Broadcast

The PV Type field is found on the General tab card.

Select one of the PV Types in Table 10 to choose which of the
transmitter’s PVs are to be sent (broadcast) to the control system.
Optionally, you can select whether the secondary variable (SV1) is
included as part of the broadcast message. The secondary is the SMV
transmitter’s meter body temperature.

NOTE:

This configuration parameter is valid only when the transmitter is in DE mode

.

Table 10

PV Type Selection for SMV Output

If You Select PV Type . . .

These PVs are Broadcast to Control

System

PV1 (DP)

Differential Pressure (PV1) measurement.

PV1 (DP) and PV2 (SP)

Differential Pressure (PV1) and
Static Pressure* (PV2) measurements.

PV1 (DP) - PV3 (TEMP)

Differential Pressure (PV1),
Static Pressure* (PV2) and
Process Temperature (PV3) measurements.

PV1 (DP) - PV4 (FLOW)

Differential Pressure (PV1),
Static Pressure* (PV2) and
Process Temperature (PV3) measurements
and the Calculated flow rate value (PV4).

PV1 (DP) w/SV1 (M.B.Temp)

Differential Pressure (PV1) measurement
with the Secondary Variable (SV1).

PV1 (DP) w/SV1 & PV2 (SP)

Differential Pressure (PV1) and
Static Pressure* (PV2) measurements with
the Secondary Variable (SV1).

PV1 (DP) w/SV1 - PV3 (TEMP)

Differential Pressure (PV1),
Static Pressure* (PV2) and
Process Temperature (PV3) measurements
with the Secondary Variable (SV1).

PV1 (DP) w/SV1 - PV4 (FLOW)

Differential Pressure (PV1),
Static Pressure* (PV2) and
Process Temperature (PV3) measurements
and the Calculated flow rate value (PV4) with
the Secondary variable (SV1).

* Static pressure may be absolute or gauge pressure, depending on the SMV model

type. (For models SMA110 and SMA125, PV2 measures absolute pressure. For
model SMG170, PV2 measures gauge pressure.)