SMV 3000 Transmitter User’s Manual

55

6.6

DPConf Configuration - PV1,

Continued

LRV and URV

PV1 (DP) Range
Values

The Lower Range Value and the Upper Range Value fields for PV1 are
found on the DPConf tab card.

Set the LRV (which is the process input for 4 mA dc* (0%) output) and
URV (which is the process input for 20 mA dc* (100%) output) for the
differential pressure input PV1 by typing in the desired values on the SCT
configuration .

LRV = Type in the desired value (default = 0.0)

URV = Type in the desired value

(default = 100 [email protected] °F for SMV models SMA125
and SMG170)
(default = 10 [email protected] °F for SMV models SMA110)

* When transmitter is in analog mode.

ATTENTION

SMV 3000 Transmitters are calibrated with inches of water ranges
using inches of water pressure referenced to a temperature of 39.2 °F
(4 °C).

For a reverse range, enter the upper range value as the LRV and the
lower range value as the URV. For example, to make a 0 to 50 inH2O
range a reverse range, enter 50 as the LRV and 0 as the URV.

The URV changes automatically to compensate for any changes in the
LRV and maintain the present span (URV – LRV).

If you must change both the LRV and URV, always change the LRV
first.