SMV 3000 Transmitter User’s Manual

57

6.6

DPConf Configuration - PV1,

Continued

About Square Root
Output,
continued

Example: If you have an application with a differential pressure range of

0 to 100 inches of water with an input of 49 inches of water,
substituting into the above formulas yields:

49

100

• 100 = 49%

49%

100

• 100 = 70% Flow, and

70% • 16 + 4 = 15.2 mA dc Output

Square Root Dropout

To avoid unstable output at PV1 readings near zero, the SMV 3000
transmitter automatically drops square root conformity and changes to
linear conformity for low differential pressure readings. As shown in
Figure 21, the square root dropout point is between 0.4 and 0.5 % of
differential pressure input.

Figure 21

Square Root Dropout Points for PV1

0

0.2

0.4

0.8

1

0.6

1.2

1.4

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0

Differential Pressure (% Full Scale)

Flow

(% Full

Scale)

0utput

(mA dc)

4

4.8

5.6

6.4

Dropout Points

22508

Sq

ua

re

R

oo

t C

ur

ve

Continued on next page