SMV 3000 Transmitter User’s Manual

59

6.7

AP/GPConf Configuration - PV2

Engineering Units

The AP/GPConf tab card displays the Low Range Value (LRV), Low
Range Limit (LRL), Upper Range Value (URV) and Upper Range Limit
(URL) for PV2 in the unit of measure selected in the Engineering Units
field.

NOTE: Depending on the SMV transmitter model type, PV2 will measure static pressure

in either absolute or gauge values.

SMV Models —SMA110 and SMA125

PV2 —Absolute Pressure

—STG170

PV2 —Gauge Pressure

PV2 Engineering Units

Select one of the preprogrammed engineering units in Table 13 for display
of the PV2 measurements.

Table 13

Pre-programmed Engineering Units for PV2*

Engineering Unit

Meaning

inH2O @ 39F

inH2O @ 68F

mmHg @ 0C

psi d

kPa

MPa

mbar

Inches of Water at 39.2

°

F (4

°

C)

Inches of Water at 68

°

F (20

°

C)

Millimeters of Mercury at 0

°

C (32

°

F)

Pounds per Square Inch

Kilopascals

Megapascals

Millibar

bar

g/cm

2

Kg/cm

2

inHg @ 32F

mmH2O @ 4C

mH2O @ 4C

ATM

inH2O @ 60F

Bar

Grams per Square Centimeter

Kilograms per Square Centimeter

Inches of Mercury at 32

°

F (0

°

C)

Millimeters of Water at 4

°

C (39.2

°

F)

Meters of Water at 4

°

C (39.2

°

F)

Normal Atmospheres

Inches of Water at 60

°

F (15.6

°

C)

d Factory setting.
* Static pressure may be absolute or gauge pressure, depending on the SMV model type.

Atmospheric Offset

For SMV models SMG170, (which uses gauge pressure as PV2 input),
you must measure the absolute static pressure and then enter that value in
the Atmospheric Offset field.

Continued on next page