8 tempconf configuration - pv3 – Honeywell SMV 3000 User Manual

Page 75

Advertising
background image

1/99

SMV 3000 Transmitter User’s Manual

63

6.8

TempConf Configuration - PV3,

Continued

Sensor Type

Identify and select the type of sensor that is connected to the transmitter as
its input for process temperature PV3. This will set the appropriate LRL
and URL data in the transmitter automatically.

Table 15 shows the pre-programmed temperature sensor types and the
rated measurement range limits for a given sensor selection.

Table 15

Sensor Types for PV3 Process Temperature Input

Sensor Type

Rated Temperature Range Limits

°

C

°

F

PT100 Dd

-200 to 450

-328 to 842

Type E

0 to 1000

32 to 1832

Type J

0 to 1200

32 to 2192

Type K

-100 to 1250

-148 to 2282

Type T

-100 to 400

-148 to 752

d Factory setting.

ATTENTION

Whenever you connect a different sensor as the transmitter’s input, you
must also change the sensor type configuration to agree. Otherwise, range
setting errors may result.

Advertising