8 tempconf configuration - pv3 – Honeywell SMV 3000 User Manual

Page 77

Advertising
background image

1/99

SMV 3000 Transmitter User’s Manual

65

6.8

TempConf Configuration - PV3,

Continued

PV3 (Temperature)
Range Values
(LRV and URV)

The Lower Range Value and the Upper Range Value fields for PV3 are
found on the TempConf tab card.

Set the LRV and URV (which are desired zero and span points for your
measurement range) for the process temperature input PV3 by typing in
the desired values on the TempConf tab card.

LRV = Type in the desired value (default = 0.0)

URV = Type in the desired value (default = URL)

Background

You can set the LRV and URV for PV3 by either typing in the desired
values on the SCT TempConf tab card or applying the corresponding LRV
and URV input signals directly to the transmitter. The LRV and URV set
the desired zero and span points for your measurement range as shown the
example in Figure 22.

Figure 22

Typical Range Setting Values for PV3

Typical RTD Range Configuration

LRL

LRV

SPAN

URV

URL

-328

-100

257

600

842 oF

Range Limits

Measurement Lower Range Upper Range

Span

Range

Value

Value

-328 to 842 oF -100 to 600 oF -100 oF

600 oF

700 oF

NOTE: LRL and URL values are set automatically when you select the sensor type in

the Sensor Type field.