9 flowconf configuration - pv4 – Honeywell SMV 3000 User Manual

Page 85

Advertising
background image

1/99

SMV 3000 Transmitter User’s Manual

73

6.9

FlowConf Configuration - PV4,

Continued

Figure 25

Graphic Representation of Sample Low Flow Cutoff Action.

1100

990

880

770

660

550

440

330

220

110

0

100

90

80

70

60

50

40

30

20

10

0

Time

100

90

80

70

60

50

40

30

20

10

0

Low Limit

High Limit

165

55

15

5

15

5

PV4 Range

GPM

%

Output

%

20.0

18.4

16.8

15.2

13.6

12.0

10.4

8.8

7.2

5.6

4.0

6.4

4.8

mA

During

Cutoff

0/
4.0*

Flow Rate

Flow Rate

enters cutoff*

Flow rate

leaves

cutoff*

* During cutoff,

output equals 0%

ATTENTION

The low flow cutoff action also applies for reverse flow in the negative
direction. For the sample shown in Figure 25, this would result in a low
limit of –55 GPM and a high limit of –165 GPM.

Continued on next page