Advertising
background image

1/99

SMV 3000 Transmitter User’s Manual

83

7.3

Running Output Check,

Continued

Procedure

Table 20

Output Check for SMV Transmitters in DE Mode

Step

Action

1

Connect SCT to SMV and establish communications. (See
Subsection 5.2 for procedure, if necessary.)

2

Be sure any switches that may trip alarms or interlocks associated
with analog loops are secured or turned off.

3

Perform Upload of the SMV database to the SCT.

4

Select General tab card and set communication mode to Digital
Enhanced.

5

Set any of the SMV transmitter PVs to output mode, by selecting the
appropriate tab cards.

DPOutCal, (for PV1)

APOutCal, (for PV2)

TempOutCal, (for PV3) or

FlowOutCal, (for PV4)

6

Enter an output value and then set PV to Output mode.

7

Open the PV Monitor window by selecting PV Monitor from the View
pull down menu. Read the PV outputs.

Also, check the PV outputs as displayed at the digital receiver.

8

Select appropriate tab card for the PVs that were set to output mode
and clear the output mode.

9

Select Status tab card to verify that all transmitter outputs are in not in
output mode and that there are no new messages.