Modbus point map – Honeywell 500 User Manual

Page 14

Advertising
background image

CLASS 500 ADVANCED KWH/DEMAND METER

62-0304—05

14

Modbus Point Map

Modbus data points available from the Class 500 meter. Listed under Class 500.

Table 4. Honeywell Modbus point map

INTEGER W FLOAT

UOM CALC. MEM

OP

DESCRIPTION

CLASS 500

1 40001 2

41001 kWh T-del NV R/W Energy

delivered

Y

2 40003 2

41003 kWh T-rec NV R/W Energy

received

Y

3 40005 2

41005 kVARh

T-del NV R/W Reactive

energy

delivered

Y

4 40007 2

41007 kVARh

T-rec NV R/W Reactive

energy

received

Y

5 41009

kW

T

R

Real

power

Y

6 41011

kVAR

T

R

Reactive

power

Y

7 41013

kVA

T

R

Apparent

power

Y

8 41015

%

T

R

Power

factor

Y

9 41017

Amps

T

R

Current

total

Y

10 41019

Amps

A

R

Current

average

Y

11 41021

Volts-N

A

R

Voltage

line-neutral

Y

12 41023

Volts-L

A

R

Voltage

line-line

Y

13 41025

Hz

A

R

Frequency

Y

14 41027

Degree

A

R

Phase

angle

Y

15

41029

kW

ØA

R

Real power, phase A

Y

16

41031

kW

ØB

R

Real power, phase B

Y

17

41033

kW

ØC

R

Real power, phase C

Y

18

41035

kVAR

ØA

R

Reactive power, phase A

Y

19

41037

kVAR

ØB

R

Reactive power, phase B

Y

20

41039

kVAR

ØC

R

Reactive power, phase C

Y

21

41041

kVA

ØA

R

Apparent power, phase A

Y

22

41043

kVA

ØB

R

Apparent power, phase B

Y

23

41045

kVA

ØC

R

Apparent power, phase C

Y

24

41047

% PF

ØA

R

Power factor, phase A

Y

25

41049

% PF

ØB

R

Power factor, phase B

Y

26

41051

% PF

ØC

R

Power factor, phase C

Y

27 41053

Amps

ØA

R

Current,

phase

A

Y

28 41055

Amps

ØB

R

Current,

phase

B

Y

29 41057

Amps

ØC

R

Current,

phase

C

Y

30

41059

Volts-N ØA

R

Voltage, line to neutral, phase A-N

Y

31

41061

Volts-N ØB

R

Voltage, line to neutral, phase B-N

Y

32

41063

Volts-N ØC

R

Voltage, line to neutral, phase C-N

Y

33

41065

Volts-L ØA

R

Voltage, line to line, phase A-B

Y

34

41067

Volts-L ØB

R

Voltage, line to line, phase B-C

Y

35

41069

Volts-L ØC

R

Voltage, line to line, phase C-A

Y

36

41071

Degree ØA

R

Phase angle, phase A

Y

37

41073

Degree ØB

R

Phase angle, phase B

Y

38

41075

Degree ØC

R

Phase angle, phase C

Y

39 41077
40 41079
41 41081
42

41083

Pulse

Auxiliary Input 1

Y

43

41085

Pulse

Auxiliary Input 2

Y

Advertising