Heat pump operation, Discovery, Enviracom furnace – Honeywell ENVIRAZONE PANEL W8835 User Manual

Page 10: Humidity, de-humidity and ventilation control, Hydronic heat operation, Thermostat operation, Rebooting microprocessor, Dual fuel equipment, Emergency heat control, Manual and automatic changeover operation

Advertising
background image

W8835 ENVIRAZONE PANEL

68-0258—04

10

Heat Pump Operation

The panel can control one or two compressor stages plus

auxiliary heat. Set DIP switch 1 and 2 to Off; set DIP switch 7

to On for a single-stage compressor and to Off for a two-stage

compressor.

Table 8. Heat Pump Equipment Configuration

Wire the reversing valve to the O/B equipment terminal. DIP

switch 9 configures this terminal to operate as an O (cool) or

B (heat) changeover terminal.

Hydronic Heat Operation

The W8835 is a forced air panel. However, it can be wired to

control hydronic valves as shown in figure 13. To control

valves or circulators on a hydronic panel, see figure 14.

Thermostat Operation

Dual Fuel Equipment

The W8835 can operate Dual fuel equipment when used with

an external fossil fuel kit. Locate the thermostat on the fossil

fuel kit instructions and wire the W8835 equipment terminals

there.

Emergency Heat Control

Emergency heat is defined as using an auxiliary heat source

without using the heat pump. The W8835 energizes the E

terminal on a call for emergency heat. The thermostat system

switch is set to Em Heat to engage this function. When active,

any zone calling for heat uses Emergency Heat, not the

compressor.

The panel energizes W3 as auxiliary heat with the Y1 and Y2

for compressor control in when not in emergency heat.

Manual and Automatic Changeover Operation

Each of the thermostats can be set for manual or automatic

changeover. If one or more thermostats call for cooling while

one or more thermostats call for heating, the panel attempts to

satisfy the greatest demand first.

Then, based on the relative demand for heating and cooling,

the panel intelligently switches between heating and cooling.

The system attempts to satisfy both the heating and cooling

demands, and does not lock out one demand in favor of the

other.

Discovery

Discovery is an automatic system configuration program where

the panel configures itself to operate with controls connected to

the EnviraCom bus. The panel enters Discovery when the

Discovery button on the panel is pressed.

Rebooting Microprocessor

To reset the microprocessor, press and release the Boot

button. The system reboots and enters the Purge mode.

EnviraCom Furnace

For furnaces with EnviraCom communications built in,

configure the panel as shown below. In this case, no

conventional equipment wiring is necessary because the

W8835 uses the 3-wire EnviraCom bus to control the HVAC

equipment. In these installations, the panel is powered from

the HVAC equipment via the 1, 2, 3 wires. Because of this, the

transformer R and C terminals on the W8835 are not used.

Instead, leave the XFMR jumpers in their default disconnected

position and wire the transformer to T1 and T2.

Table 9. Furnace Type Configuration

Humidity, De-humidity and
Ventilation Control

The panel can control humidity, de-humidity, and ventilation by

receiving messages from the VisionPRO® IAQ thermostat.

The thermostat designated as zone 1 will have control of these

functions. Configure this thermostat as found in the installation

instructions for the thermostat.

The humidity, de-humidity, and ventilation terminals are all dry-

contact terminals; the relay contacts close when active. So

devices that need dry contact control like a ventilator can be

wired directly to the VENT terminals, or a steam humidifier can

be wired directly to the HUM terminals. Devices that need to be

powered like a ventilation damper or some models of

evaporative humidifiers are wired using the VENT or HUM

terminals wired through the R terminal as shown in Fig. 3.

If using a Honeywell TrueSteam humidifier, configure the zone

one VisionPRO IAQ thermostat installer setup #374 to "3", and

wire the TrueSteam GF terminal to the HVAC fan terminal, and

wire the TrueSteam GT terminal to the G on the W8835.

NOTE: When controlling a steam humidifier, set all thermo-

stats to HEAT. Do not set thermostats to AUTO. This

prevents the panel from humidifying on zone 1, when

another zone is calling for cooling. Alternatively, set

zone 1 thermostat Installer Setup 374 to “2” to allow

humidification only during calls for heat.

Equipment Type

DIP 1

DIP 2

Heat Pump

Off (Down)

Off (Down

Compressor Stages

DIP 7

1 Stage

On (Up)

2 Stage

Off (Down

Heat Pump Changeover

DIP 9

O (Cool)

On (Up)

B (Heat)

Off (Down

Type of Equipment

DIP 3

Conventional

On (Up)

EnviraCom

Off (Down)