11

68-0258—04

Discharge Air Temperature Sensor
DATS

The C7835A1009 Discharge Air Temperature Sensor (included

in the Y8835 kits) is a supply-duct-mounted temperature

sensor probe used to control capacity and prevent high plenum

temperatures or coil-icing. The sensor is wired to the

EnviraCom bus using three wires. When a high or low limit is

reached, the panel shuts off the equipment and keeps the fan

operating for a minimum of two and one-half minutes. After this

time, and any applicable minimum-off times imposed by the

HVAC equipment. It re-energizes the equipment when the

discharge air has recovered by ten degrees. When the high or

low limit is exceeded, the Heat (red) or Cool (green) LED on

the DATS flashes.

When the DATS is in a limit condition, the Heat, Cool and

Purge LEDs on the W8835 panel continue to operate as if the

DATS were not turning the equipment off.

The high and low limit is set on the DATS. The high

temperature limit is set from 110°F to 160°F with a small

screwdriver or using fingers and the low limit is set at 40°F or

48°F degrees with a jumper.

Circuit Breaker Protection

A built-in thermal circuit breaker protects the EnviraZone panel

against shorts in the damper wiring and EnviraCom bus. It

does not protect against shorts in the HVAC equipment wiring

into the panel.

When the circuit breaker is tripped, none of the LEDs illuminate

and the yellow rectangular component located bottom center

on the panel is hot to touch.

• Remove power to the panel for at least five minutes to allow

the circuit breaker to cool off and reset.

• To eliminate the short, verify the dampers and transformer

wiring.

Fan On In Heat

The system blower can be set to come on with a call for heat

as required for hydro-air or electric heat systems. Set the

blower function using DIP switch 8. When configured for heat

pump, this DIP switch is not used.

Table 10. Fan-in-heat Configuration

Adding Additional Zones

Connect one W8703 to the EnviraCom bus to expand the

system up to six zones or connect two W8703 to control up to

nine zones:

• Wire the first three zone dampers and thermostats to the

W8835 Envirazone Panel.

• Wire the additional dampers to the W8703 panels.

• Set the DIP switches on the W8703 to correspond to the

zones being controlled. See W8703 Installation Instructions.

• Wire terminals 1, 2, and 3 from the additional thermostats to

terminals 1, 2, and 3 on any of the panels.

TROUBLESHOOTING

Table 11. Troubleshooting

DIP Switch 8

Fan Control

Off (Down)

Fan on in heat by panel.

On (Up)

HVAC control of fan.

Symptom

Possible Cause

Action

No LEDs are Illuminated.

No power to the board.

Check for 24 Vac (±10%) across R and C.

Transformers out of phase.

If 48 Vac across R and T1, reverse T1 and T2 wires.

Shorted wire.

Check thermal circuit breaker. If hot, a short exists in wiring.

Damper LEDs on, but no

other LEDs illuminate on a

call for heat, cool, or fan.

Insufficient voltage.

Check for 24 Vac (±10%) across R and C.

Incorrect configuration.

Check jumpers and DIP switches for correct configuration.

Heat pump operates

incorrectly or not at all.

Incorrect wiring.

Verify equipment terminals wiring.

Incorrect configuration.

Verify DIP switches configuration.

No damper LEDs are

illuminated.

Incorrect configuration.

Verify that XFRM jumpers are set correctly.

Error 35 or 39 message on

thermostats.

Incorrect zone numbers.

Verify the thermostat zone numbers are set correctly (1,2,3 etc)

Wait is continuously in the

thermostat display

Incorrect configuration

Verify dip switch 3 is set to conventional (Up) position. If
controlling a heat pump, verify that thermostats are not configured
to lockout the compressor based on outdoor temperature.
(This feature is not used on zoned applications)