Table 12. DIP Switches 1 and 2

Table 13. DIP Switches 3–10

Equipment Type

DIP 1

DIP2

1 Stage Conventional

On (up)

On (up)

2 Stage Conventional

On (up)

Off (down)

3 Stage conventional

Off (down)

On (up)

Heat Pump

Off (down)

Off (down)

DIP Switch

Function

On (Up, Default)

Off (Down)

3

Type of furnace

Conventional/non-communicating

EnviraCom Communicating

4

Purge time

Two minutes

3.5 minutes

5

Fan control during purge

HVAC controlled

Panel controlled

6

Damper control during purge Last zone(s) calling open during purge

Open all dampers during purge

7

Heat pump compressor

stages

One stage

Two stages

8

Fan control in heat

Fan controlled by panel in cool and

HVAC equipment in heat

Fan controlled by panel in heat and

cool

9

Heat pump changeover

O (Cool changeover)

B (heat changeover)

10

Not used