W8835 ENVIRAZONE PANEL

3

68-0258—04

Dampers:

See Table 1 for suggested dampers. Dampers are connected to

M1 Common, M4 Open, and M6 Closed (see Fig. 5 through 8

for hookups). Connect no more than five ARD or ZD dampers

to an individual zone.

Connect no more than five ARD or ZD dampers to the panel

when using one 40 VA transformer; connect no more than

ten ARD or ZD dampers when using two 40 VA transformers.

Use SDCR for additional dampers required. If using RRD

dampers, refer to RRD installation instructions for maximum

number of dampers.

Fig. 1. W8835 dimensions in in. (mm).

Table 1. Recommended Dampers

Motor Terminal

Damper Action

Common/M1

Common

Open/M4

Power Open

Closed/M6

Power Close

Honeywell Damper Type

Round

Rectangular

For systems > 2000 cfm.

MARD or RRD

For recommended dampers, call the Honeywell

Zoning Hotline at 1-800-828-8367.

For systems <= 2000 cfm.

ARD or RRD

ZD

M20594

10-3/4

(273)

12-3/4

(324)

1-7/8

(47)

HEAT

COOL

PURGE

FAN

EM. HT.

COMM

ZONE 1

ZONE 2

ZONE 3

TM