W8835 ENVIRAZONE PANEL

68-0258—04

8

CAUTION

Equipment Damage Hazard.

Incorrect transformer wiring can damage panel.

Wire transformers in phase when one transformer

is wired to R and C and the auxiliary transformer

is wired to T1 and T2.

Fig. 12. Wiring transformer(s) to panel.

Wiring C7835 Discharge Air
Temperature Sensor

Connect wire terminals 1, 2, and 3 to the corresponding

terminals on either the W8835 EnviraZone panel or any other

EnviraCom device such as a thermostat. Refer to C7835

Installation Instructions for configuration. Multiple devices can

be wired in parallel to the each of the 1, 2, 3 terminals.

STARTUP AND CHECKOUT

1. Verify that the equipment, thermostats, transformer, and

Discharge Temperature Sensor are wired correctly. If

one transformer is powering the panel, install the XFRM

jumper. If two transformers are powering the panel, leave

the XFRM jumper in the open position.

2. Power up the W8835. Verify that all LEDs except COM

illuminate for five seconds.The board should then enter

the Purge mode with all dampers open. The damper

LEDs are green to indicate the dampers are open.

The COM LED begins to blink.

3. Press the Purge Override button to terminate the Purge

mode.

4. On the W8835 Panel, set the DIP switches.

a. Set DIP switches 1, 2, and 7 to assign the

appropriate number of heating and cooling stages.

See Tables 5 and 6.

b. Configure other DIP switches, as necessary to fit the

application. See Table 6.

5. On each thermostat, enter the Installer Setup procedures

using the VisionPRO® IAQ Installation Instructions and

assign each thermostat a zone number to correspond

with its zone damper.

6. Run Discovery by pressing the Discovery button on the

zone control panel.

7. On each thermostat, enter the Installer Setup

procedures using the Installation Instructions and config-

ure other pertinent Installer Setup options. Program the

thermostat schedule if the default settings are not

desired.

8. Run Discovery by pressing the Discovery button on the

panel.

9. Set Zone one thermostat to heat and raise the setpoint to

call for heat.

a. Verify that the heat LED is red.

NOTE: The furnace heat may not come on immedi-

ately. Allow at least 5 minutes for heat to begin

after the thermostat calls for heat.

b. Verify that Zone one LED remains green.

c. Verify that all other zone LEDs are not illuminated.

d. Change thermostat mode from Heat to Off.

10. Set Zone two thermostat to heat and raise the setpoint to

call for heat.

a. Verify that the heat LED is red.

b. Verify that Zone two LED remains green.

c. Verify that all other zone LEDs are not illuminated.

d. Change thermostat mode from Heat to Off.

11. Alternatively, set a thermostat to Cool, lower the

setpoint to call for cooling, wait five minutes, and verify

correct operation.

OPERATION

Sequence of Operation

When there is no call for heat, cool or fan, the board is in the

idle mode, indicated with no system LEDs illuminated, see

Table 3. Damper LEDs are green to indicate open. On a call for

heat, cool, or fan, the calling zone damper stays open and the

damper LED remains illuminated; the other zone dampers

close and corresponding damper LEDs do not illuminate.

The W8835 panel energizes the HVAC equipment and

conditioned air is delivered to the calling zone. The heat LED

(red), cool LED (green), or fan LED (green) illuminates to

indicate equipment operation.

The fan LED illuminates only on a call for fan; it does not

illuminate during a call for heat or cool. When the heat/cool call

is satisfied, the system enters the Purge mode, indicated by

the Purge LED (yellow). Damper positions either remain in the

same positions as at the end of the call for heat or cool

(default) or open, depending on the position of DIP switch 6.

After purge, all dampers return to the Open position.

R
C

T1
T2

C R

C

R

24 VAC, 40 VA

TRANSFORMER

(REQUIRED IF

MORE THAN

FIVE DAMPERS)

24 VAC, 40 VA

TRANSFORMER

DAMPER

XFRM

PANEL

XFRM

M31126

REMOVE XFRM JUMPERS

FROM PINS WHEN USING

TWO TRANSFORMERS