T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

62-0255—07

14

Setup Procedure

The Setup process uses a hierarchical menu structure
that is easy to use. You press the W and X arrow buttons
to move forward and backward through the menus.

NOTE: The menus can display only those relays that

are defined in Setup (see “1.3.2. NBR OF
RELAYS” on page 21). For example, if you con-
figure only two relays, then only two relays dis-
play on the appropriate menus.

To change the controller’s sensors and output setup
parameters, perform the following procedures in the order
listed:

1. Enter Setup mode — see “1.1. Entering Setup

Mode”

2. Setup Sensors — see “1.2. Setting up the Sensors”
3. Setup Outputs — see “1.3. Setting up the Outputs”

on page 17

4. Exit Setup Mode — see “1.4. Exiting Setup” on

page 24

1.1. Entering Setup Mode

To enter Setup mode, press and hold the MENU button
for five seconds to display the Setup menu. See Fig. 23
on page 12.

Fig. 24. Setup - Sensors Menu.

1.2. Setting up the Sensors

1. From the Setup menu, use the S and T buttons to

highlight SENSORS.

2. Press the X button to display the Sensors menu.

Fig. 25. Setup - Sensors - Number of Sensors.

1.2.1. Number of SENSORS

The value entered here determines the number of
sensors displayed on the home screen.

NOTE: For applications that do not use Reset, only one

sensor (Sensor A) is available for use.

1. From the Sensors menu, highlight # SENSORS then

press the X button to display the number of sensors.

2. Use the S and T buttons to enter the number of

sensors (1 or 2).

Default: 2

3. Press the X button to accept the value and display

the SENSOR A selection.

Fig. 26. Setup - Sensors - Sensor A Menu.

1.2.2. SENSOR A

If you are implementing two-sensor reset control, Sensor A
must always be the controlled temperature and Sensor B must
always be the controlling temperature. For example, in a reset
control based on outside temperature, Sensor A must be the
inside sensor and Sensor B must be the outside sensor.

1. From the Sensors menu, highlight SENSOR A.
2. Press the X button to display the Sensor A selec-

tions.

The menu selections change depending on whether the
sensor type is 1097

Ω

PTC (temperature) or 0-10V / 4-

20MA.

SETUP

SENSORS

SETUP

SENSORS

# SENSORS

SENSOR A

SENSOR B

EXIT

M24586

ENTER

NUMBER OF

SENSORS

SETUP
SENSORS

# SENSORS

SETUP

SENSORS

# SENSORS

2

M24587

SETUP
SENSORS

SENSOR A

SETUP

SENSORS

SENSOR A

TYPE

UNITS

CALIBRATE

LABEL

EXIT

SETUP

SENSORS

SENSOR A

TYPE

UNITS

MIN VAL

MAX VAL

CALIBRATE

LABEL

EXIT

SENSOR A

TYPE = PT1000

SENSOR A

TYPE = 0-5V, 0-10V,

OR 4-20MA

M24588A