T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

62-0255—07

22

Fig. 48. Setup - Outputs - Options - Min Off/On Time.

1.3.3.2. MIN OFF

or

MIN ON

This is the minimum number of seconds of “off time” or
“on time” for all relays.

1. Press the X button to display the Min Off/On value.
2. Use the S and T buttons to increase/decrease the

desired number of seconds from 0 to 990 seconds
in 10 second increments.

Default: 0 (zero)
Range: 0 to 990 seconds

3. Press the X button to accept the seconds and

display the DI OPTIONS.

NOTES:

1.

The minimum off time applies to all relay
outputs.

2.

When minimum off time is active, relays
waiting to be energized display a flashing
square underneath the relay number on the
home screen.

3.

If the minimum off time is not equal to zero
(0), the minimum off time activates at power-
up. To manually override, press the W button
at any time.

Fig. 49. Setup - Outputs - Options - DI Options.

1.3.3.3. DI OPTIONS (digital input options)

The DI Option you select applies to all outputs. This
option overrides any Setpoint/Setback values entered in
the Schedule.

1. Press the X button to display the DI Option selec-

tions.

2. Use the S and T buttons to highlight DISABLE,

SETBACK, or IGNORE.

Default: DISABLE

3. Press the X button to accept the value and display

the SHOW RT option.

When the digital input (DI) closes, all outputs follow the DI
option value (Disable, Setback, or Ignore):
DISABLE disables the outputs; relays return to de-

energized state and Mod outputs return to 0% output.

SETPOINT forces the control to the setpoint

temperature.

SETBACK enables a setback temperature value to be

programmed for each output.
— To program the Setback temperature with Reset,

see Fig. 73 on page 31.

— To program the Setback temperature without

Reset, see Fig. 60 on page 26.

ENABLE energizes all relays to 100%. Use this option

carefully.

IGNORE causes the digital input to have no effect on

the Relay or Mod outputs.

M24610A

SETUP

OUTPUTS

OPTIONS

ENTER

MINIMUM

OFF TIME

FOR RELAYS

SETUP

OUTPUTS

OPTIONS

MIN OFF

0

SEC

OR

MIN ON

SETUP

OUTPUTS

OPTIONS

MIN ON

0

SEC

MIN OFF

ENTER

MINIMUM

ON TIME

FOR RELAYS

SETUP
OUTPUTS

OPTIONS

DI OPTS

SETUP

OUTPUTS

OPTIONS

DI OPTS

SELECT DI

OPTIONS

FOR

OUTPUTS

DISABLE

SETPOINT

SETBACK

ENABLE

IGNORE

M24611A

Advertising