T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

62-0255—07

30

Fig. 69. Program - Sensor A Min. Setpoint.

3.2.3. SP MIN A2 or BOILER MIN

(Setpoint minimum for Sensor A)

1. From the menu, use the S and T buttons to high-

light BOILER MIN or SP MIN A2.

2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the

desired minimum setpoint temperature.

Default: 140°F (60°C)
Range: -40°F to 248°F (-40°C to 120°C)

4. Press the X button to accept the setpoint tempera-

ture and display the next option.

Fig. 70. Program - Sensor B Min. Setpoint.

3.2.4. RESET B2 or OUTSD MAX

(Sensor B value when at MIN A2 Setpoint)

1. From the menu, use the S and T buttons to high-

light RESET B2.

2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the

desired setpoint temperature.

Default: 60°F (16°C)
Range: -40°F to 248°F (-40°C to 120°C)

4. Press the X button to accept the value and display

the next option.

Fig. 71. Program - Throttling Range or Differential.

3.2.5. THROTTLING RANGE or
DIFFERENTIAL

Throttling Range displays for Modulating outputs.
Differential is used for the Relay outputs.

1. From the menu, use the S and T buttons to high-

light THROT RNG or DIFFERNTL.

2. Press the X button to display the throttling range

value.

3. Use the S and T buttons to increase/decrease the

desired value.

Default: 20°F (-6.6°C)
Range: 1°F to 150°F (1°C to 66°C)

4. Press the X button to accept the value and display

the next option.

The Throttling Range brackets the setpoint setting, e.g., if
the setpoint is 72°F and the throttling range is 10°F, then
the effective throttling temperature range is 67°F to 77°F.

In heating mode, the Differential is below the setpoint.
The relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the Differential, the relay energizes.

In cooling mode, the Differential is above the setpoint.
The relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
Differential, the relay energizes.

ENTER

MINIMUM

SETPOINT FOR

SENSOR A

PROGRAM
MOD

1

SP MIN A2

MENU

PROGRAM

MOD 1

SP MIN A2

160

F

o

M24574

ENTER

SENSOR B VALUE

FOR MINIMUM

SETPOINT

PROGRAM
MOD

1

RESET B2

MENU

PROGRAM

MOD 1

RESET B2

70

F

o

M24575

ENTER

THROTTLING

RANGE FOR

FOR MOD 1

PROGRAM
MOD

1

THROT

RNG

MENU

PROGRAM

MOD 1

THROT RNG

20

F

o

M24577