T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

31

62-0255—07

Fig. 72. Program - Action Selection.

3.2.6. ACTION

For the MOD 1 output (and for outputs with RESET=NO),
the ACTION selection displays.

For all other outputs with RESET=YES, the ACTION
selection does not display; continue with “3.2.7.
SETBACK OFFSET (if configured)” on page 31.

1. From the menu, use the S and T buttons to high-

light ACTION.

Default: HEAT

2. Press the X button to display the action selections.
3. Use the S and T buttons to select the desired

value.

4. Press the X button to accept the highlighted selec-

tion and display the next option.

Fig. 73. Program - Setback (Offset).

3.2.7. SETBACK OFFSET

(if configured)

The Setback temperature option displays only if
scheduling is enabled (see Fig. 47 on page 21) or the DI
Option is set to Setback. (see Fig. 49 on page 22).

This value is the number of degrees plus (+) or minus (-)
that you want the temperature to be offset from the
setpoint.

For example, If you want the temperature to be 10°F less
than the setpoint during setback mode, enter -10°F. In
normal operations for heating, the offset will be negative.
For cooling, the offset will be a positive value.

1. From the menu, use the S and T buttons to high-

light SETBACK.

2. Use the S and T buttons to increase/decrease the

desired setpoint temperature.

Default: 0°F
Range: -150°F to 150°F (-101°C to 66°C)

3. Press the X button to accept the value and display

the menu.

This completes the programming of the MOD 1 output.
To program the second Modulating output and the two
relays, continue with “3.3. Second Modulating Output and
Relays”.

PROGRAM
RELAY

1

ACTION

MENU

PROGRAM

RELAY 1

ACTION

SELECT

ACTION

FOR

RELAY 1

HEAT

COOL

REV ACT

DIR ACT

HUMID

DEHUMID

M24578

PROGRAM
RELAY

1

SETBACK

MENU

PROGRAM

RELAY 1

SETBACK

-10

F

o

ENTER

SETBACK

SETPOINT

FOR RELAY 1

M24579

Advertising